岩土力学 ›› 2021, Vol. 42 ›› Issue (5): 1434-1442.doi: 10.16285/j.rsm.2020.1104

• 岩土工程研究 • 上一篇    下一篇

越冬基坑水平冻胀的防治措施效果分析

沈宇鹏1,王笃礼2,林园榕1,汤天笑1,刘欣1   

  1. 1. 北京交通大学 轨道工程北京市重点实验室,北京 100044;2. 中航勘察设计研究院有限公司 技术质量部,北京 100098
  • 收稿日期:2020-08-16 修回日期:2021-01-04 出版日期:2021-05-11 发布日期:2021-05-08
  • 作者简介:沈宇鹏,男,1977年,博士,教授,主要从事冻土路基方面的研究
  • 基金资助:
    国家自然科学基金(No. 41772330);冻土工程国家重点实验室开放基金(No. SKLFSE201808);中央高校基本科研业务费专项资金资助(No. 2019YJS119)

On the effect of prevention measures against horizontal frost heave of foundation pits over winter

SHEN Yu-peng1, WANG Du-li2, LIN Yuan-rong1, TANG Tian-xiao1, LIU Xin1   

  1. 1. Beijing Key Laboratory of Track Engineering, Beijing Jiaotong University, Beijing, 100044, China; 2. Technical Quality Department, AVIC Institute of Geotechnical Engineering Co. Ltd., Beijing, 100098, China
  • Received:2020-08-16 Revised:2021-01-04 Online:2021-05-11 Published:2021-05-08
  • Supported by:
    This work was supported by the National Natural Science Foundation (41772330), the Open Fund of the State Key Laboratory of Frozen Soil Engineering (SKLFSE201808) and the Fundamental Research Funds for the Central Universities in China (2019YJS119).

摘要: 近年来,季节性冻土区越冬基坑工程因水平冻胀引起的事故频发,但相关防冻胀措施的研究成果较少。开展了北京昌平区桩锚支护结构越冬基坑现场监测,分析了越冬基坑的土体水分迁移、支护结构受力状态、护坡桩水平位移等冻胀特性的演化规律;建立了水热力耦合模型,通过与监测数据对比,验证了模型的正确性;以温度场分布、护坡桩水平位移和支护结构水平冻胀力为指标,利用数值计算结果,对比了保温层和换填非冻胀土两种措施及设置参数对水平冻胀的抑制效果,提出了有效的防冻胀措施。研究表明:基坑土体冻结由竖向水分迁移和侧向水分迁移共同作用引起;铺设保温层对冻胀的抑制效果明显好于换填非冻胀土,且更加经济可行,容易操作,因此推荐在实际工程中使用。研究成果可为今后寒区工程的支挡结构设计施工提供理论支持。

关键词: 越冬基坑, 水平冻胀, 桩锚支护结构, 水热力耦合, 冻胀措施

Abstract: In recent years, accidents caused by horizontal frost heave frequently occur in foundation pit projects over winter in seasonally frozen soil areas, but there are few researches on anti-frost heave measures. In this paper, the field monitoring of foundation pits over winter of pile-anchor supporting structures in Changping District of Beijing is carried out, and the evolution law of frost heave characteristics such as soil moisture migration, stress state of supporting structure and horizontal displacement of slope protection pile is analyzed. A hydro-thermal coupling model is established, and the model is verified by comparing the results with the monitoring data. Taking the temperature field distribution, horizontal displacement of slope protection pile and horizontal frost heaving force of supporting structure as indexes, using numerical calculation results, the suppression effects of insulation layer and replacement of non-frost heaving soil and setting parameters on horizontal frost heaving are compared, and the effective anti-frost heaving measures are put forward. Studies have shown that the freezing of foundation pit soil is caused by the combined action of vertical and lateral water migration; the inhibition effect of laying an insulation layer on frost heaving is significantly better than replacing non-frost heaving soil. Laying an insulation layer is recommended to be used in projects since it is more economical, feasible and easier to operate. The research results can provide theoretical support for the design and construction of supporting structures in cold areas in the future.

Key words: foundation pit over winter, horizontal frost heave, pile-anchor retaining structure, thermal-hydro-mechanical coupling, frost heave measures

中图分类号: 

  • TU 470
[1] 田亚护,胡康琼,邰博文,沈宇鹏,王腾飞,. 不同因素对排水沟渠水平冻胀力的影响[J]. , 2018, 39(2): 553-560.
[2] 杨校辉 ,朱彦鹏 ,郭 楠 ,黄雪峰 , . 地铁车站深基坑桩锚支护结构内力试验研究[J]. , 2014, 35(S2): 185-197.
[3] 李 岩 ,刘 波 ,张建新,. 竖向直排冻结条件水平冻胀力试验研究[J]. , 2014, 35(11): 3199-3206.
[4] 许海勇 ,陈龙珠 ,刘全林 . 桩锚支护结构水平位移的简化算法[J]. , 2013, 34(8): 2323-2328.
[5] 许锡昌,葛修润. 基于最小势能原理的桩锚支护结构空间变形分析[J]. , 2006, 27(5): 705-710.
[6] 王铁行 ,李 宁 ,谢定义,. 土体水热力耦合问题研究意义、现状及建议[J]. , 2005, 26(3): 488-493.
Viewed
Full text


Abstract

Cited

  Shared   
  Discussed   
[1] 魏 丽,柴寿喜,蔡宏洲,王晓燕,李 敏,石 茜. 麦秸秆加筋材料抗拉性能的实验研究[J]. , 2010, 31(1): 128 -132 .
[2] 黄庆享,张 沛,董爱菊. 浅埋煤层地表厚砂土层“拱梁”结构模型研究[J]. , 2009, 30(9): 2722 -2726 .
[3] 荆志东,刘俊新. 红层泥岩半刚性基床结构动态变形试验研究[J]. , 2010, 31(7): 2116 -2121 .
[4] 刘争宏,廖燕宏,张玉守. 罗安达砂物理力学性质初探[J]. , 2010, 31(S1): 121 -126 .
[5] 王登科,刘 建,尹光志,韦立德. 突出危险煤渗透性变化的影响因素探讨[J]. , 2010, 31(11): 3469 -3474 .
[6] 樊恒辉,高建恩,吴普特,娄宗科. 水泥基土壤固化剂固化土的物理化学作用[J]. , 2010, 31(12): 3741 -3745 .
[7] 张成平,张顶立,骆建军,王梦恕,吴介普. 地铁车站下穿既有线隧道施工中的远程监测系统[J]. , 2009, 30(6): 1861 -1866 .
[8] 王 军,曹 平,李江腾,刘业科. 降雨入渗对流变介质隧道边坡稳定性的分析[J]. , 2009, 30(7): 2158 -2162 .
[9] 张 渊,万志军,康建荣3,赵阳升. 温度、三轴应力条件下砂岩渗透率阶段特征分析[J]. , 2011, 32(3): 677 -683 .
[10] 张雪婵 ,龚晓南 ,尹序源 ,赵玉勃. 杭州庆春路过江隧道江南工作井监测分析[J]. , 2011, 32(S1): 488 -0494 .