土壤电阻率测量影响因素的试验研究

周 蜜1,王建国1,黄松波1, 2,豆 朋2,张丽镪1,姚 伟1   

  1. 1. 武汉大学 电气工程学院,武汉 430072;2. 广东电网公司佛山供电局,广东 佛山 528000
  • 收稿日期:2010-09-29 出版日期:2011-11-01 发布日期:2011-11-09
  • 通讯作者: 王建国,1968年生,博士,教授,博士生导师,主要从事雷电防护与接地技术、高电压绝缘与测试技术教学和科研工作。E-mail: wjg@whu.edu.cn E-mail:zhoumi927@whu.edu.cn
  • 作者简介:周蜜,男,1986年生,博士研究生,主要从事雷电防护与接地技术方面的研究工作

Experimental investigation on influencing factors in soil resistivity measurement

ZHOU Mi1,WANG Jian-guo1,HUANG Song-bo1, 2,DOU Peng2,ZHANG Li-qiang1,YAO Wei1   

  1. 1. School of Electrical Engineering, Wuhan University, Wuhan 430072, China; 2. Foshan Electric Power Supply Bureau, Guangdong Electric Power Grid Co., Foshan, Guangdong 528000, China
  • Received:2010-09-29 Online:2011-11-01 Published:2011-11-09

摘要: 实验室测量的土壤电阻率准确性受到电极布置以及测试信号类型等影响。选取5种不同质地土壤,比较了四极法与二极法测量以及四极法测量中电压极探针渗入深度的影响,分析了直流信号与交流信号的测试差别以及电流强度及交流频率的影响。结果表明,二极法测量结果包含了土壤与电极的接触电阻,且随土壤含水率降低接触电阻不断增大;四极法可在电压极渗入深度较浅,即土壤扰动较小的情况下测量;土壤在直流电压下存在极化效应,土壤电阻率测量宜采用交流;土壤热容量有限,对电阻率在200 Ω•m以内的土壤测量的电流密度不宜超过1 mA/cm2;土壤电阻率随测量频率增加而逐渐下降。

关键词: 土壤电阻率, 二极法, 四极法, 接触电阻, 极化效应

Abstract: Accuracy of soil resistivity measuring result in the laboratory will be influenced by electrodes arrangement, types of test signal, etc. Five types of soils with different textures are selected to investigate the influencing factors of soil resistivity measurement. A comparison of resistivity measuring results between four-electrode method and two-electrode method is made firstly; and the influence of potential electrode penetrations in four-electrode method is also studied. A comparison between the resistivity measuring results with DC and AC voltage test signal is made. Moreover, influence of the current density and AC signal frequency on soil resistivity measuring results has also been investigated here. The results have shown that, measuring results by two-electrode method contain the contact resistance between electrodes and the soil, which will increase rapidly when the water content of soils decreases. The soil resistivity test can be performed with little penetration, or little disturbance to the tested soils by the four-electrode method. Alternating current test signal should be used to prevent polarization effect of DC voltage. Due to the fact that thermal capacity of the test soil is limited, current densities should be kept less than 1 mA•cm-2 to test soils with electrical resistivity less than 200 Ω•m. Soil resistivity has been found to be decreased as test signal frequency increases.

Key words: soil resistivity, two-electrode method, four-electrode method, contact resistance, polarization effect

中图分类号: 

  • TU 411
[1] 李 瑛,龚晓南,张雪婵. 电压对一维电渗排水影响的试验研究[J]. , 2011, 32(3): 709-714.
Viewed
Full text


Abstract

Cited

  Shared   
  Discussed   
[1] 沈 扬,周 建,龚晓南,刘汉龙,. 考虑主应力方向变化的原状软黏土应力应变性状试验研究[J]. , 2009, 30(12): 3720 -3726 .
[2] 李利平,李术才,张庆松. 岩溶地区隧道裂隙水突出力学机制研究[J]. , 2010, 31(2): 523 -528 .
[3] 张 文,王泽文,乐励华. 双重介质中的一类核素迁移数学模型及其反演[J]. , 2010, 31(2): 553 -558 .
[4] 李丽华,陈 轮,高盛焱. 翠湖湿地软土触变性试验研究[J]. , 2010, 31(3): 765 -768 .
[5] 胡亚元. 利用EVP模型确定堆载预压法的卸载时机[J]. , 2010, 31(6): 1827 -1832 .
[6] 章定文,韩文君,刘松玉. 初始应力各向异性状态下圆柱孔扩张机制分析[J]. , 2010, 31(S2): 104 -108 .
[7] 洪 勇,孙 涛,栾茂田,郑孝玉,汪发武. 土工环剪仪的开发及其应用研究现状[J]. , 2009, 30(3): 628 -633 .
[8] 张乾兵,朱维申,李 勇,孙林锋,张 磊. 洞群模型试验中微型多点位移计的设计及应用[J]. , 2011, 32(2): 623 -628 .
[9] 张虎元 ,赵天宇 ,吴军荣 ,严耿升 ,冯 蕾. 膨润土改性黄土衬里防渗性能室内测试与预测[J]. , 2011, 32(7): 1963 -1969 .
[10] 李京爽,侯瑜京,徐泽平,梁建辉,张雪东,宋献慧. 砂土自由场地基水平垂直振动离心模拟试验[J]. , 2011, 32(S2): 208 -214 .